Equivalent Tests of Links of 50 MVA STATCOM

SONG Qiang,ZHANG Dong-jiang,CHEN Tian-jin,TENG Le-tian,ZHENG Dong-run
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.12.013
2006-01-01
Abstract:The 50MVA STATCOM to be installed at Shanghai Xijiao substation employs chain-circuit inverter based on IGCTs.For strict type tests,it's necessary to do equivalent rated-state operational tests and overcurrent protection tests for each link.The so called back-to-back test method is employed for the equivalent rated-state operational tests,two Links are connected back-to-back via an inductor,one is controlled to operate in leading mode and another in lagging mode,power losses are provided by a DC power supply connected to one of the dc capacitors.The equivalent overcurrent protection test is carried out through a inductive load.The parameters of the links,the principle and the results of equivalent tests are given in this paper.Tests results confirmed that all performance requirements were met.
What problem does this paper attempt to address?