+-50 Mvar STATCOM Based on Chain Circuit Converter Employing IGCT'S

刘文华,宋强,滕乐天,郑东润,张东江
DOI: https://doi.org/10.3321/j.issn:0258-8013.2008.15.009
2008-01-01
Abstract:The ±50 Mvar STATCOM based on chain circuit converter employing IGCTs has been developed successfully and has been put into operation. The main circuit configuration and parameters, the 150 Hz optimal PWM (pulse width modu- lation) control scheme, the DC voltage balance control scheme, the var control scheme based on linearization via feedback and the field test results are given in this paper. Field test results confirmed that all performance requirements were met.
What problem does this paper attempt to address?