50 MVA Statcom with Igct Chain Inverter

ZHENG Dong-run,QIAO Wei-dong,LIU Wen-hua,SONG Qiang
2005-01-01
Abstract:Statcom based on chain inverter has more advantages than statcom based on inverter of multipletransformer. The main technical indices of 50 mva statcom were introduced. The main circuit composition of 50 mva statcom based on igct chain inverter, and the strategy of pwm control based on harmonic optimization were given. The operating test of equivalent rated condition was adopted for fully loaded routine test of the installation, the principle and testing results of equivalent rated condition test were given in the paper. The testing result shows that the design of chain link has reached the technical requirements of chain statcom.