SIMULATION STUDY ON THE RUNNING STRATEGY OF THE ±50 Mvar STATCOM

朱永强,崔文进,胡东辰,滕乐天,王伟,俞旭峰
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.21.017
2004-01-01
Abstract:Research and simulation on the system running strategies of the ±50 Mvar STATCOM in Xijiao Transformer Substation, Shanghai, are presented. Based on the data of Shanghai power system and according to the system situation, the main control targets of the dynamic voltage supporting and daily voltage regulating for the α50 Mvar STATCOM are analyzed. Running strategies of the α50 Mvar STATCOM are studied and determined, in which the reactive power is limited in a certain range for daily voltage regulating in order to store certain dynamic and reactive reservation. Once fast or obvious voltage variations take place, the STATCOM can pour out reactive power as much as possible to support the voltage. The scheme of cooperating with one of the two existing 30 Mvar switched capacitors in the substation is also discussed, in which the cooperative 30 Mvar capacitor is always kept in operation and the STATCOM is allowed to work at reductive area so that there is more reactive power reserved to deal with dynamic voltage variations. Simulation results in PSASP verify the feasibility and validity of the proposed running strategies.
What problem does this paper attempt to address?