BALANCING CONTROL OF DC VOLTAGES OF 50MVA STATCOM BASED ON CASCADE MULTILEVEL INVERTERS

刘文华,宋强,滕乐天,王伟,魏文辉,耿俊成
DOI: https://doi.org/10.3321/j.issn:0258-8013.2004.04.027
2004-01-01
Abstract:Combined with the development of a 50MVA STATCOM based on IGCT, the steady state mathematical model of DC capacitor voltages for STATCOM based on cascade multilevel inverters is established, the mechanism of DC voltage unbalance is explained and the various measures to control the balancing of the DC voltages are analyzed in this paper. The balancing control scheme based on energy exchange through a DC bus is proposed. The principle of balancing control scheme based on energy exchange through an AC bus is analyzed and the control method of tracking the maximum (or minimum) DC voltage is proposed. The proposed control method is studied with simulation on the PSCAD model of the 50MVA STATCOM and with experiments on a ±18kvar STATCOM installation. The simulation and experimental resu- lts show the correctness and the feasibility of the mathematical model and the proposed control method.
What problem does this paper attempt to address?