Balancing Compensation of 3-Ph Unbalanced Load with Cascade Inverters Based STATCOM

罗承廉,林烽,刘遵义,纪勇,刘文华
DOI: https://doi.org/10.3969/j.issn.1674-3415.2003.10.002
2003-01-01
Abstract:Due to the separate phase control capability, low output current harmonics and fast response characteristics, cascade inverters based STATCOM is suitable for balancing compensation of 3-Ph unbalanced load. Main circuit configuration and integrated voltage-reactive power control scheme for balancing compensation with cascade inverters based STATCOM is proposed. The 3-Ph compensation current is obtained through vector transform with symmetrical weight method. The single phase reactive power is calculated with single phase instantaneous reactive power concept. Selective harmonics eliminated PWM (SHE-PWM) is employed to ensure that the THD of output current is less than 5% and the DC voltage is controlled. Simulation results verify the effects of the fast response of output reactive power for balancing the unbalanced load.
What problem does this paper attempt to address?