Optimized Energy-saving Operation of High-voltage High-capacity STATCOM
LEI Liebo,LI Yong,HU Guangzhen,ZHANG Yongkang,ZHANG Haitao,YUAN Zhichang
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.02.033
2013-01-01
Abstract:In order to achieve the energy-saving operation of high-voltage high-capacity static synchronous compensator(STATCOM),we discussed the switch choice,controlling method,and controlling strategies of STATCOM based on the 35 kV/±200 MVA cascade STATCOM adopted in China Southern Power Grid.After comparing the opening and closing losses and the driving power of IGBT,IGCT and IEGT,it is suggested that IEGT is the best choice from the aspect of energy saving.Furthermore,we analyzed the disadvantages of PWM inverter,and proposed to adopt an assistant-resonant soft-switching topology in PWM controlling inverters of the target system,which could reduce the operating loss and deal with the conflicts among the carrier frequency,reactive power waveform and device losses of inverters.Considering the parallel operation of target STATCOM,an energy-saving optimizing mathematic model of multiple parallel connected STATCOM for establishing energy-saving operation strategy was established.Moreover,analyzing the transient reactive power requirements of Guangdong Power Grid,we proposed a cooperating controlling strategy for STATCOM and existing reactive power compensation devices:STATCOM act firstly,then turn into/out the capacitor or reactor when the compensation capacity was at the setting quota.Further simulative and experimental data indicate that,by using the proposed methods,about 30% of the STATCOM loss can be saved.