DEVELOPMENT OF ±20 Mvar STATCOM EMPLOYING GTO INVERTERS

Liu Wenhua,Liang Xu,Jiang Qirong,Luo Chenglian,Liu Zunyi
DOI: https://doi.org/10.3321/j.issn:1000-1026.2000.23.005
2000-01-01
Abstract:To improve the stability of power transmission system in He'nan Province, He'nan Electric Power Company and Tsinghua University have jointly investigated and developed ± 20 Mvar STATCOM employing GTO inverters. The STATCOM consists of four six-pulse voltage source inverter units rated 5 MVA each which use 48 GTOs rated 4. 5 kV/4 kA each to eliminate the 12 k ± 1 (k=1, 2, 3⋯)order harmonic components in the output voltage. A new type of GTO overcurrent protection. GTO turn-off low loss snubber circuit and a new method of suppressing DC over-voltage are proposed. The controller adopts a duplex system. Its functions, including sampling, control calculation and pulse generating, are all implemented with high-speed digital processing method based on 32-bit TMS320C31 DSP chip. The STATCOM has been installed in a 220 kV substation and has been put into operation successfully since April 1999. The field tests were carried out to verify the performance and the long-term reliability of the installation. The outline, technical features and field test results of the ±20 Mvar STATCOM are given. This project is the original Power Ministry Science and Technology Key Project.
What problem does this paper attempt to address?