Abstract:This paper analyzes the generation process of the overvoltages V(DSP), V(DM) and V(R) during the turn-off process of GTO and the measures to suppress the overvoltages. Through analyses of the features of conventional RCD snubber circuit and three kinds of low-loss snubber circuit, the snubber circuit for the 4500V/4000A GTOs in a 20MVA STATCOM installation is proposed. The snubber circuit is the low-loss Delta -type snubber circuit with clamping capacitor. Experimental results demonstrate that the proposed Snubber circuit is very effective for large capacity two-level GTO inverter.