An Analysis of the Water Wall Modification Scheme for a Chinese-made Once-through Boiler

唐人虎,胡志宏,陈听宽,罗毓珊
DOI: https://doi.org/10.3969/j.issn.1001-2060.2002.06.027
2002-01-01
Abstract:A hydrodynamic analysis was conducted in connection with the modification scheme of a 300 MW once-through boiler at Yaomeng Power Plant. On the basis of a comparison of the boiler water-wall negative and positive flow-rate response characteristics existing prior to and after the modification the authors noted the poor hydrodynamic characteristics of the furnace water-wall composed of vertical tube coils. An excessively high water-wall temperature and the big difference in metal and inter-tube fluid temperatures leading to tube explosion can mainly be attributed to the high mass flow speed and the resulting negative flow rate response characteristics. The above discovery may provide a helpful guide during the modification of analogous boilers.