Research on Current Interruption by Grounding switch Used in 750kV Double-circuit Transmission Lines | Badania pra{ogonek}du przerwania w uziemionym przeła{ogonek}czniku używanym w podwójnej linii transmisyjnej 750 kV

Ji Shengchang,Ou Xiaobo
2013-01-01
Abstract:In order to interrupt electromagnetically and electro-statically inductive current with high amplitude, grounding switches are applied in double-circuit transmission lines. In this paper, the formula of the induced voltage and current are drawn under different condition of grounding switch installed on the maintenance line. In order to clarify the characteristics of every electrical parameter, after calculating the capacitance and inductance matrix of 750kV double circuit transmission lines, simulation research is conducted using EMTP-ATP. Inductive voltage and current of 750kV doublecircuit transmission line are calculated and analyzed. Furthermore, in order to classify the worst switching parameter of grounding switches, the steady-state currents and the transient recovery voltage (TRV) are also calculated and analyzed. And then, the tests of capacitive and inductive current interruption for a 800kV grounding switch are also carried out in the laboratory. The results of the simulation and experiment in this paper provide guiding opinions for selecting grounding switches used in the 750kV double-circuit transmission lines.
What problem does this paper attempt to address?