Overvoltage Mechanism of Switching off Shunt Reactors for 40.5 Kv Vacuum Circuit Breakers

XU Guozheng
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2012.33.018
2012-01-01
Abstract:Accidents occurred frequently in the 35 kV power system in recent years when vacuum breaker switched off shunt reactors.However,the reason is not clear.Through data statistics,detailed summary and analysis were carried out on the numerous results of field test.Statistic results shows that there can be 128 reignitions during a break operation,the three phase reignition process can last to 5 ms,the RRRV of the latter reignition phase can be as high as 13 kV/ms,the inter-phase overvoltage can beyond 8.0 pu and the phase to ground overvoltage can beyond 4.0 pu.The statistics results show that the main reason of such accidents is three phase multi-reignitiion and inter-phase overvoltage.Based on circuit theory,the mechanism of the whole process of the three phase multi-reignition was analyzed and revealed.The magnitude of the prospective transient recovery voltage is high enough to lead arc reignition,the high frequency current generated by the reignition can be coupled into the other two phases and cause forced arc extinguish.The magnitude and RRRV of the phase of forced arc extinguish are both extremely high,then excite the multi-reignition process andgenerate the inter-phase overvoltage which is twice in magnitude to phase to ground one.