Three-phase Modeling of Vacuum Circuit Breakers Switching off Shunt Reactors

杜宁,关永刚,张景升,牛继荣,姚树华,徐国政
DOI: https://doi.org/10.13296/j.1001-1609.hva.2010.03.002
2010-01-01
Abstract:Aiming at the operating conditions of 40.5 kV vacuum circuit breaker switching off shunt reactors,and in order to eliminate deficiencies in the existing simulation model,a general review of simulating researches on vacuum circuit breakers switching off small reactive current is given.A three-phase model of 40.5 kV circuit breakers switching off shunt reactors is set up based on the experimental results of a type of 4.5 kV vacuum circuit breaker,including the dielectric strength characteristics,high-frequency current quenching criteria and chopping current.And the interphase coupling is considered in the model.A three-phase simulation is conducted for the transient process of the vacuum circuit breaker switching off shunt reactors via ATP-EMTP,and the simulation results coincide almost with experimental results.
What problem does this paper attempt to address?