Fault Arc Modeling and Analysis in Circuit Breaker in HVDC Converter Station Filter Branch

WANG Bin,WEI Xiangxiang,ZHANG Guohui,WEN Boying,FENG Yingchun,DONG Xinzhou
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.170373
2018-01-01
Abstract:Circuit breaker (CB) in filter branch is switched frequently to keep balance of reactive power in HVDC (high voltage direct current) substation. The switching of CB to capacitor is easy to cause transient overvoltage, and even CB explosion accident. But the existing arc model cannot accurately simulate this dynamic arcing process in CB because they are mostly based on power frequency arc extinguishing principle. In response to this problem, dynamic arc resistance was found to be the key factor for accurate simulation firstly in paper based on analysis of real recorded data in substation, pre-arcing stage was divided into the pre-breakdown stage and incomplete arc stage,the full arc extinction stage was divided into the pre-arcing extinction stage and arc went out stage and then an improved quadratic dynamic arc model based on high frequency arc extinguishing principle was proposed. Comparison of simulation and real data verifies the accuracy of the proposed model, and then based on this model, the dynamic characteristics of CB arc breakdown voltage, current and resistance were analyzed, which provide a basis for the research of identification and early warning of arcing fault in CB.
What problem does this paper attempt to address?