Circuit Breaker Arc Fault Detection Based on Fault Recording Data in HVDC Converter Station

Bin Wang,Xinzhou Dong,Bin Yu,Min Xie,Haigang Wang
DOI: https://doi.org/10.1049/cp.2020.0096
2020-01-01
Abstract:Arc fault occurs easily when circuit breakers (CB) cut the AC filters circuits in HVDC substation frequently. A transient arc model and online detection method are proposed in this paper. The proposed arc model is based on the conventional three stages arc model and Mayr arc model, the simulation results coincide with the actual recorded data well. And also, by utilizing the zero sequence arc current, the online arc detection method based on first order accumulation is introduced. Simulation results and actual arc fault data proved the correctness and accuracy of proposed arc fault detection algorithm.
What problem does this paper attempt to address?