Symmetry-component analysis for fault on common-tower double-trensmission line narrow line-to-line distance

HUANG Shao-feng,ZHANG Hai,FAN Xin
2012-01-01
Abstract:On account of the mutual inductance parameter feature of common-tower double-transmission line with narrow line-to-line distance which is common in 220kV power system,a practical fault analytic approach based on average mutual inductance parameter of parallel lines is proposed.The new approach can deal with both single-circuit-line fault and interline fault on common-tower double-transmission line.Via using the narrow line-to-line distance parallel lines' average mutual inductance instead of phase-coupling and line-coupling which have similar values,the fault on double-circuit lines can be simplified to an equivalent fault on a single-circuit line and can be analyzed with symmetric component method.It makes the analysis easy and simplifies the calculation greatly by avoiding using six-sequence modulus.The comparison of calculation examples to ATP-EMTP simulation shows that the new analytic approach can give credible calculation only with little and reasonable errors.The new approach is based on practice parallel lines,and it has the advantages of having definite physical meaning and simplicity.
What problem does this paper attempt to address?