Symmetrical fault analysis at AC transmission line with back-to-back MMC-HVDC considering controller characteristics

Haozong Wang, Shenxing Shi, Xinzhou Dong
DOI: https://doi.org/10.1049/cp.2020.0084
2020-01-01
Abstract:Modular Multilevel Converter(MMC) represents the most advanced technology innovation of high voltage direct current(HVDC) systems. Back-to-back MMC-HVDC is a widely used structure for connecting two AC systems and enhancing transmission capacity. However, fault analysis of MMC integrated systems is a non-trivial problem due to the complex characteristics of MMC and its controller. We note that although existing mathematic tools cannot solve the whole problem, it is still possible to analyse symmetrical fault at AC lines. The following assumptions are made to obtain a simplified model: 1) The fault type is symmetrical fault (3-phase fault); 2) The fault is so severe that it can lead to a high voltage drop at the point of common coupling(PCC); 3) Orders of outer-loop controllers shall not change during the fault period. Under these assumptions, a closed-form formula of fault current at PCC is derived under s-domain and d-q frame. To verify our work, a simulation model of 3-phase fault on a transmission line with back-to-back MMC-HVDC is built using PSCAD/EMTDC software. Comparisons between theoretical calculation and simulation results show that the proposed fault current can describe the general trend of fault current in a relatively accurate way.