Adopting Some Arresters to Suppress Switching Overvoltage Deeply in 1000kV UHV Transmission Line
CHEN Shuiming,XU Wei,HE Jinliang
DOI: https://doi.org/10.3969/j.issn.1003-6520.2006.12.003
2006-01-01
Abstract:The idea of adopting some arresters installed along line to suppress switching overvoltage deeply in UHV is realized in this paper. Based on the UHV transmission line project, effects of arrestor’s number and position on switching overvoltages, including three phases energizing line with no load, single phase auto-reclosing and overvoltage caused by fault are calculated by using the electromagnetic transient program PSCAD/EMTDC. The calculation shows that in the case without any arresters installed along line, the maximal overvoltage of three phases energizing line with no load, single phase auto-reclosing and overvoltage caused by fault are 1.83, 1.83 and 1.53 p.u.. respectively. When arresters are applied along line, the three overvoltage can be suppressed to 1.50, even lower than 1.50 pu, which means arresters along line is a good measure to suppress switching overvoltage in UHV. Besides amplitude of overvoltage, another main factor considered in this paper is the energy passing arresters. Calculation results show in three ovevoltages above, maximal energy passing single arrester is 2107.94 kJ, 866.43 kJ and 17.32 kJ respectively. And maximal total energy passing arrestors of one phase is 3534.67 kJ, 1215.61 kJ and 86.06 kJ respectively. By comparing the results, it is found that more arresters used along line, lower the overvoltage is, different position where arresters are placed effects the result of suppressing, and the maximal difference of overvoltage caused by position is 0.07 p.u.. Calculation of the energy shows that total energy passing arrestors of one phase generally increases with the arrestor's number increasing, but for any single arrestor, the energy decreases. In the case of single phase auto-reclosing, the energy decreases from 866.43 kJ to 337.68 kJ when the number of arrester along line increases from 1 to 4. In the case of three phases energizing line with no load, energy decreases from 2107.94 to 958.67 while arrester’s number increases from 1 to 4.