Method Comparison for Thermal Calculation of Water Jacket Heater

Wei-bo ZHENG,Dong SUN,Zhen TANG,Lu FAN,Xiu-li YANG,Xiao-feng HU,Wei ZHANG
DOI: https://doi.org/10.3969/j.issn.1000-7466.2018.03.006
2018-01-01
Abstract:As problems,the phenomenon that exit gas temperature almost retains unchanged and the flame tube exit gas temperature decreases with the increase of excess air coefficient are en-countered during the original calculation of a heater design per to SY/T 0535—94 Thermal and Resistance Calculation Method about Fire Tube Type Heater.The calculation results is found not agreed with the field test results and the calculation is rechecked with the general thermal calcula-tion method for boilers fired by oil or gas.Conformance results are obtained and a further analy-sis show s the method in SY/T 0535—94 ignores the effect of gas constituents on heat transfer and enlarges heat transfer ability of gas tube w hich results in the calculating results based on SY/T 0535—94 do not agree with the experimental results.A new standard that the influence of flue gas components and fly ash on heat transfer be take into account is suggested to publish.
What problem does this paper attempt to address?