Influence of Non-uniform Current Distribution on Energy Absorption Capability of Multi-column Parallel ZnO Arrester

Xilei CHEN,Ke YANG,Zhengjie HE,Dongju WANG
DOI: https://doi.org/10.3969/j.issn.1673-7598.2017.03.016
2017-01-01
Abstract:Multi-column parallel arresters are often adopted in HVDC transmission projects in order to decrease protection level and satisfy high energy demand,but there is a problem of the non-uniform current distribution between the columns because of VI characteristic deviation,which influences the energy absorption capability of the multi-column arrester.The theoretical analysis of the arrester energy absorption capability considering the non-uniform current distribution is presented.The results show that the little deviation of V-I characteristic will result in notable non-uniform current distribution;the non-uniform current distribution decreases the energy absorption capability of a n-column arrester corresponding to n/β times that of one column arrester;in order to satisfy the current sharing between the columns,the deviation of discharge voltages shall not be more than 1%,to insure the current distribution nonuniform coefficient β is not more than 1.1.