Characteristics of the Delayed Current-zero Crossing of Short-circuit Current Occurred in the UHV Series Compensated Transmission Line

GUAN Yonggang,GUO Peiqi,XIANG Zutao,XU Guozheng,LIU Weidong
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.11.028
2015-01-01
Abstract:The delayed current-zero crossing of short circuits current can happen in UHV systems with series-compensation when fault occurs and can create difficulties to the circuit breakers to interrupt. This paper analyzed the mechanism of the above phenomenon based on the typical parameters of 1000kV double circuit transmission line in China. The key reason for the delayed current-zero crossing of current passing through the circuit breaker which is far away from the series compensation is that the bypass flowing of periodic content of fault current through non-fault line which caused by the action of MOV in the series compensation. The factors that influenced the delayed current-zero crossing have been studied, such as fault type, fault location, line length, series compensator arrangement and series compensation degree. According to the simulation results, it is recommended to take the dispersed arrangement of series compensation and improve the capacity of circuit breaker to solve this problem, opposed to apply opening resistances on the circuit breaker in UHV line with series-compensation.