Research on Ultra-high-voltage GIS On-site Lightning Impulse Withstand Voltage Test Transient Over-voltage and Its Restraining Method

Binwei JI,Yonggang GU,Zirui LIU,Anxiang GUO,Shuai WANG,Tao WEN,Qiaogen ZHANG
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.02.013
2018-01-01
Abstract:Gas insulated switchgear(GIS)has been widely used in electrical power system.During the on-site lightning impulse withstand voltage test of GIS,when the underproof GIS discharges,high-amplitude oscillating overvoltage will take place,which may threaten the intact equipments.In this paper,we developed a ATP-EMTP transient analyzing model of ultra-high-voltage GIS on-site lightning impulse withstand voltage test system and fault arc.The over-voltage amplitude and its restraining method has been investigated.The results show that the calculated voltage waveforms matches well with the test waveforms,indicating that the fault arc model can simulate the discharging process accurately.The fringe nodes in the test system will cause the total reflection of transient voltage,making the over-voltage amplitude higher than 2 400 kV.The over-voltage amplitude on top of the no-load bushing can be restrained after the introduction of the low-damping transient voltage restrainer.The parameter Cr=800 pF、Rr=100 Ω is suggested,which can effectively make the oscillating voltage lower than 2 400 kV.