Improvement Measures for Electric Unbalance of Double-Circuit Transmission Lines on Same Tower

ZHANG Bin,CHEN Shuiming,ZHUANG Chijie,ZHANG Bo,DENG Shicong
DOI: https://doi.org/10.13335/j.1000-3673.pst.2014.12.034
2014-01-01
Abstract:Asymmetric electric parameters of doublecircuit transmission lines will lead to unbalance of current and voltage, influencing the economy and reliability of the system operation. Analysis indices of electric unbalance and computation methods for the indices were introduced in this paper. A simulation model of transmission lines was constructed, and improvement measures for electric unbalance of double-circuit transmission lines were also researched. Analysis results show that drum-shaped tower and reverse phase sequence arrangement of conductors will lower zero sequence and negative sequence unbalance degree. Decreasing distance between the double-circuit transmission lines can obviously lower negative sequence unbalance degree, but slightly raise zero sequence unbalance degree. To minimize electric unbalance degree, conductors should be arranged in reverse phase sequence and transposed in reverse direction for one single cycle transposition. For two cycle transpositions, conductors should be transposed in the l/6-l/6-l/3-l/6-l/6 way. Capacitor compensation can significantly decrease negative sequence unbalance degree. With the increase of the length of line, the effect of capacitor compensation increases gradually.