Analysis of Safety Protection Measures for Maintenance Work of 500 kV Double-Circuit Transmission Lines on Same Tower

Qi Yang,Dehua Zou,Jianjun Zhang,Hui Li,Jianping Chen,Jinliang Li
DOI: https://doi.org/10.1088/1757-899x/199/1/012127
2017-05-01
IOP Conference Series: Materials Science and Engineering
Abstract:Four transmission lines on the same tower are widely used because of their obvious economic and social benefits. But it also has high power supply reliability, so the choice of reasonable maintenance mode is particularly important. In this paper, we deducted the maintenance influence of the energized line to non-energized line, calculated and analyzed protection measures of non-energized singular line of 500kV double-circuit transmission line on the same tower with ATP software, and calculated field intensity distribution of typical operating position of the energized double-circuit transmission line with the finite element software. The calculation shows that when using the outage maintenance method, hanging both ground current and personal security line can reduce the current flowing through the operator's body effectively. When using the live maintenance method, the field intensity of operator body strengths up to 383.69kV/m, The operator needs to wear shielding cloth with at least 43.08 dB shielding efficiency, in order to meet the security requirements.
What problem does this paper attempt to address?