Characteristics of Transient Recovery Voltage of 66 Kv Circuit Breaker in 500 Kv Substation

CHEN Shui-ming,XU Wei,YANG Peng-cheng,LIU Wei-guo
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.06.015
2009-01-01
Abstract:Large transient recovery voltage(TRV) may cause the circuit breaker(CB) damaged.Researches of TRV in China are mainly focus on UHV and EHV CB,while,TRV on CB of distribution network should also be paid close attention to.TRV of 66 kV CB in 500 kV substation is researched with electromagnetic transient program PSCAD/EMTDC.The results show that while the bus without loads interrupted,the rising rate of recovery voltage(RRRV) reached up to 5.67 kV/μs;while the fault currents interrupted,the RRRV reached 3.71 kV/μs,which are much larger than the limit value 2.2 kV/μs.Adopting capacitance is an effective way to decrease the TRV and RRRV.6 nF surge parallel capacitance bank is suggested to be installed,and the RRRV can be reduced to 2.16 kV/μs.