Effects of 500 kV Current-Limiting Inductors on Transient Recovery Voltage and Its Countermeasures

Chen Shui-ming,Xu Wei,Wang Zhen-xing,Ge Cheng
DOI: https://doi.org/10.3969/j.issn.1003-9171.2008.01.003
2008-01-01
Abstract:Air-cored current-limiting inductor(CLI) is used to limit the magnitude of fault current in 500 kV power system.While limiting short circuit current,effects of CLI on transient recovery voltage(TRV) are researched in this paper.Combining with the project of East China power system, the effects of CLI on TRV is analyzed in detail.The results show that the effect of three-phase short circuit is serious than that of single-phase short circuit,and parallel capacitor can reduce the TRV,but the capacitance is too large.
What problem does this paper attempt to address?