Experimental Study on the Solid-state Fault Current Limiter with Bypass Inductance

张鹏飞,江道灼,刘华蕾
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.04.014
2005-01-01
Abstract:In order to evaluate the control strategy and working effects of the prototype of a solid-state fault current limiter with bypass inductance in 10 kV/500 A/2 500 A (maximal virtual value of fault current), a corresponding experimental model in 50 V, 1 A/5 A is designed. Based on this strategy, an experiment has been made on the model in different short circuit faults. The results of experiment indicate that the mixed-mode inversion and subsequent flow strategy, which is used by the solid-state fault current limiter, can not only limit the short circuit current to the proposed level, but also has many advantages such as the simplicity and reliability of the control method and the exact judgment of the fault types, the capability of decreasing the load of fly-wheel thyristor T7 and T8 to a low level in the course of limiting or disconnecting the short circuit current.
What problem does this paper attempt to address?