Research on Grounding Method of Arc-Suppression Coil with Parallel or Serial Resistance and Ground-Fault Protection Principle

MOU Long-hua,ZHOU Wei,YUE Qing-yu
DOI: https://doi.org/10.3321/j.issn:0253-9993.2009.08.027
2009-01-01
Abstract:Through analyzing and comparing the operation characteristics of systems grounded via arc-suppression coil with parallel or series resistance,it was pointed that the grounding method of arc-suppression coil with parallel resistance should be adopted,and a principle of ground-fault protection based on the fusion of active power and harmonics power of fault components was proposed together with the corresponding model of action criterion,with which the difference of fault judging quantity between the fault feeder and sound feeder can be increased effectively.This principle is with very good selectivity to ground fault in compensated distribution networks.
What problem does this paper attempt to address?