Optimization of air flow field for direct air cooling units
Haibo SHUI,Xiaolong WANG,Tao ZHANG,Yanfeng SONG,Lei CHEN,Xinming XI,Lijun YANG,Xiaoze DU
DOI: https://doi.org/10.3969/j.issn.1002-3364.2015.03.081
2015-01-01
Abstract:The air flow field of air cooling unit in direct air cooling systems has dramatic spiral trend and is cen-trosymmetric distributed,resulting in a very uneven distribution of cooling air volume in finned tube bundles,a real-ly low utilization efficiency of the heating surface of finned tubes and quite poor flow and heat transfer performance of air cooled condenser.Thus,the CFD software was applied to investigate the dynamic characteristics of air flow field inside the direct air cooling unit.It finds that due to sudden change of flow area at the fan outlet,flow dead zone and vortexes form at the air cooling unit bottom and serious reflux occurs in the unit center,causing an increase in flow resistance,which impedes the cooling air to flow from the fan outlet toward the finned tube bundles.There-fore,four flow guidance schemes were put forward and thermal performance of the air cooling unit in these four schemes were analyzed.The results show that,after guidance of the cooling air inside the air cooling unit,the air flow field is optimized,the bundles'surface flow and temperature field are more uniform and the flow and heat trans-fer property of the air cooling unit are significantly improved.