Diagnosis and Analysis Methods of Main Transformer Fault Point Using Differences between TAs

HUANG Hao-sheng,CHEN Jiu-lin,LU Yang,YUAN Yu-bo,LI Peng
DOI: https://doi.org/10.3969/j.issn.1009-0665.2012.04.005
2012-01-01
Abstract:How to accurately locate the failure point when the transformer fails makes the fault treatment difficult.Taking a fault treatment of 500 kV transformer as an example,the information of protective action and fault waveforms is analyzed comprehensively.The casing fault current in high-mid voltage side of the main transformer does not change its polarities before and after the fault and owns ride-through characteristics.However the diffevential protection using independent TA can detect the differential current and act,so it can determine that the short-circuit fault point is located between transformer casing TA and independent TA,and offer references for the fault maintenance of the transformer.