Test and Fault Analysis for High Power High Frequency High Voltage Transformer

Yan-an WANG,Deng-ming XIAO,You-huai LI,Jin GU,Gui-wen CHEN
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.05.024
2009-01-01
Abstract:In order to analyze the fault reason of a high power high frequency high voltage transformer, a test platform was established, zero-load test and wave-recording of a fault transformer and a normal transformer were carried out, and the wave characteristic was analyzed. Taking combination of the insulation structure of the transformer, an equivalent circuit of the transformer considering distribution parameters was put forward, and a simplified equivalent circuit was put forward. First, the fault reason which may lead to growth of inputting zero-load current of the transformer is stray capacitances other than air gap abnormity. Second, through the method of current wave comparing, the conclusion that the transformer fault is caused by the insulation breakdown of high voltage winding can be drawn. The diagnosis result is authenticated through the observation after dismantlement of the transformer.