Improvement of Electro-geometric Model with Considering Lightning Strike Angle

李瑞芳,吴广宁,曹晓斌,马御棠,刘平
DOI: https://doi.org/10.16188/j.isa.1003-8337.2009.04.006
2009-01-01
Abstract:Electro-geometric model(EGM) is one of the effective methods to compute shielding failure rate of transmission lines.Lightning strike angle was not considered in traditional EGM,which directly supposed that the direction on lightning strike is vertically downward.Shielding failure rate was obtained through calculating projecting length of protection arc and exposure arc.In order to make the EGM more close to practical situation,in the paper it was supposed firstly that lightning strike angle varies in a plane.To each definite angle,protection arc and exposure arc are projected on direction which is vertical to the lightning strike angle.Then shielding failure rate on each definite lightning strike angle was calculated according to the length of protection arc and exposure arc.Considering comprehensively the value of shielding failure rate on each definite lightning strike angle and probability of lightning strike angle,the formula is given to calculate shielding failure rate after considering probability of lightning strike angle.As an example,for a 220 kV substation located at plain,a probability rate 9.97% of shielding failure was obtained at 25 kA of lightning current and strike angle φ[0~π/2).The improved calculating method is closer to simulate practical situations because of considering lightning strike angle,which is useful to research on the transmission line shielding failure rate.