Heat transfer and irreversibility in a dimpled fin in an air-cooled condenser

SONG Weiming,LI Zhixin
2010-01-01
Abstract:The air flow and heat transfer around a dimpled fin in an air-cooled condenser were numerically studied.The irreversibility of the convective heat transfer was analyzed based on the entransy concept.The results show that the heat transfer is significantly enhanced in a single row tube heat exchanger with dimpled fins in a direct air-cooled condenser compared with a plain fin candenser.The heat transfer performance of the staggered dimple pattern is better than the in-line pattern with the same number of dimples for Reynolds numbers between 600 and 1 500.The Nusselt numbers for the staggered pattern are enhanced 30%~55%,while the friction factors are increased by 50%~85% compared with the plain fins.The performance evaluation criterion(PEC) of the staggered dimple fin then reaches 1.14~1.27.The equivalent thermal resistance defined by the entransy dissipation in the dimple fins is much less than in the plain fin.Therefore,the heat transfer irreversibility in the dimple fins is reduced,which is the physical mechanism for their better heat transfer performance.