Analysis of Capacitive Voltage Rise During Off-Line Partial Discharge Tests on Power Transformers

Wang Xuan,Cao Xiao-long,Li Yun-ge,Liu Ying
DOI: https://doi.org/10.1007/s11741-007-0510-1
2007-01-01
Journal of Shanghai University (English Edition)
Abstract:Partial discharge test on a transformer is carried out according to the items in IEC 60. During the test, unproved measuring system is calibrated by proved system at a voltage no less than 50% the rated testing voltage. The result is then extrapolated linearly, leading to an error related to the distribution of stray capacitance, which varies with the testing frequency, especially to large transformers. In this paper a factor, named the capacitive rise fact, is introduced to assess the rise. The factor can be adjusted to some extent by changing the reactance that is connected to the LV side of the testing circuit to lower the capacity of the power source. However, the factor changes when the voltage divider on the high voltage side is removed after the voltage ratio has been calculated, and a great error is resulted under unfavorable conditions.
What problem does this paper attempt to address?