Study on on-line calibration of partial discharge in power transformers

Xuzhu Dong,Changchang Wang,Zhong Wang,Shengyou Gao,Weihong Jing,Dezhi Hao,Weiping Ma,Lianghua Zheng
1997-01-01
Abstract:Calibration of discharge quantity is required for on-line monitoring of partial discharge in power transformers. Traditional off-line calibration can not meet the requirements of on-line monitoring. This paper describes one of usually used on-line calibration methods, the pulse injection method through tapping of capacitive bushing. The influences of inductance, capacitance of bushing tapping and multi-point grounding of the tank on the injected pulse wave and sensibility in on-line calibration are discussed. Laboratory simulations and on-site tests show that this method is practicable for on-line calibration within engineering permissible error range under definite conditions.
What problem does this paper attempt to address?