DEVELOPMENT OF ON-LINE MONITORING SYSTEM FOR PARTIAL DISCHARGE WITHIN POWER TRANSFORMER

罗日成,李卫国,熊浩,邓本再
DOI: https://doi.org/10.3321/j.issn:1000-3673.2004.16.012
2004-01-01
Abstract:A set of on-line monitoring system for partial discharge within power transformers is developed. On the basis of electro-acoustic joint monitoring method the presented system can detect the current signals of multiplex pulses and the ultrasonic signals caused by partial discharge within the power transformer. In the hardware of this system the anti-interference measures such as optical fibre transmission and so on are used to effectively suppress the on-site electromagnetic interference; in the software of this system the discrete binary wavelet transform algorithm is used to filter the periodical interference and corona interference in monitored signals, so that the internal and external discharge pulses can be accurately distinguished. Based on equivalent sound velocity and using fuzzy theory and finite element numerical analysis, the position where the partial discharge occurs can be located. The on-site operation experience shows that the presented system possesses higher detection accuracy and can offer creditable basis for condition-based maintenance of power transformers.
What problem does this paper attempt to address?