RESEARCH AND DEVELOPMENT OF ON-LINE MONITORING SYSTEM WITH PARTIAL DISCHARGE IN XLPE POWER CABLES

赵中原,吕征宇,段乃欣,邱毓昌
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.05.013
2004-01-01
Abstract:Monitoring partial discharge (PD) is an important means to assess the electrical insulation condition of XLPE power cables. In China, the frequency of the method used in PD detection of the XLPE power cables is low. Hence an electromagnetic coupling method with wide frequency bandwidth is presented. The electromagnetic coupling system consists of Rogowski coil, amplifier, filter and digital oscillograph. Detection of several simulated defects and XLPE cables with artificial defects shows that this method provides high sensitivity compared with the IEC 60270 method. This detection system can detect PD signal and recognize different defects.
What problem does this paper attempt to address?