Radio-frequency Detection of Partial Discharge in Power Cable Joints

Xiao Hu,Shaocai Yang,Qing Du,Xiangrong Chen,Fuxin Tang
DOI: https://doi.org/10.1109/tpwrd.2023.3334310
IF: 4.825
2024-01-01
IEEE Transactions on Power Delivery
Abstract:Partial discharge (PD) is indicative of insulation defects in power cable joints. Cross-bonding cable joints have a break in the joint shield that interrupts the screen of the jointed cables. It is possible for radio frequency (RF) signals of PD in the joints to emit from the shield break. This paper presents the use of off-the-shelf RF sensors at the shield break for non-intrusive PD detection. Measuring results from a 35 kV XLPE cable joint sample with artificial defects suggest that PD-induced electric and magnetic fields can be detected simultaneously with this approach. Typical pulses measured are limited to approximately 500 ns in duration, and the FFT spectrum of the pulses is mainly distributed at frequencies below 200 MHz. Average pulse magnitude ranging from about 6 to 22 mV can be measured between 10-15 kV. Increasing the measuring distance can cause the measured pulse magnitude to decease exponentially. Additionally, numerical simulations show that reducing the length of the shield break can cause the pulse magnitude recorded at the shield break to decrease gradually. The presented approach can potentially be used for cost-effective and non-intrusive detection of PD in cross-bonding cable joints.