UHF Signal External Detection of Partial Discharge in Transformers
WANG Song,ZHAO Xiao-hui,FANG Xiao-ming,LI Yan-mu,LI Yan-ming
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.08.021
2007-01-01
Abstract:Partial discharge(PD) is a symptom of the insulation deterioration in transformers.Detecting PD,therefore,is an important strategy to monitor the condition of the insulation system of transformers.Several techniques are applied to this field including acoustic,electrical and chemical methods.Ultra High Frequency(UHF) technique which is developed in recent years is one of the electrical methods.Through detecting UHF E-M waves emitted from PD sources,PDs could be detected in transformers.UHF detection technique has some advantages that the measuring frequency is high,much interference such as corona can be rejected,the SNR(signal noise rate) is high and the sensitivity and the reliability are both good.Usually,UHF sensors are installed in the transformer tank.However,there will be potential peril for transformers in service.The effect of transformer tank on UHF wave propagation is analyzed in this paper.The feasibility of using external UHF sensor for detecting partial discharge activities is discussed,and then outside propagation characteristic of UHF E-M wave is experimentally studied.The results show that UHF signals could leak outside the transformer through the cracks after multiple refraction and reflection in the transformer tank.An antenna outside the tank could receive the signals.The size of the crack will influence the strength of the received signal,the bigger the crack is,the bigger the strength will be.Meanwhile,the research results show that UHF signal can be received around the bushing.