Field test on a transformer for partial discharge location by uwb-rf method

S. Zheng,C.R,Z. Tang,W. Chang,Y. Jiang,W. He,R. Lu
2011-01-01
Abstract:Locating Partial Discharge (PD) sources accurately in power transformers is of great importance for maintenance scheduling, maintenance efficiency and even operational risk analysis. A new method based on the differences between propagation times of Radio Frequency (RF) signals was proposed initially in 2003, since then this method has attracted much attention due to its high sensitivity and noise-immunity and constant improvements on this method have been conducted by the researchers. This paper described the in-field verification work in China, an Ultra Wide Band (UWB, 1-5GHz) RF PD location system was developed and applied in PD location experiments on a 220kV power transformer. The experiment result shows that the RF location method has a high precision, the locating errors are less than 30cm for the partial discharge sources occurred in internal or external winding, which meets the needs of the practical use.
What problem does this paper attempt to address?