Location of Partial Discharge in Transformer by Energy Ratio Method

Junfeng GUI,Wensheng GAO,Zhensheng WU,Kexiong TAN
DOI: https://doi.org/10.13336/j.1003-6520.hve.2006.01.014
2006-01-01
Abstract:To locate partial discharge(PD) source in power transformer by electrical way,a method based on the energy ratio at different terminals is proposed.The relationship curve between energy ratio of signals and PD location is determined.After PD happens and signals are measured,the ratio is calculated for locating PD through the curve.Simulation analysis with a numerical model and imitating experiment on transformer winding are carried out.It is found that the ratio of PD energy under 1 MHz possesses a good characteristic to the position.The relationship can be predigested to a simplified representation for a convenient use in the field.Results indicate that the locating accuracy of these methods,with the error less than 10%,is satisfied for engineering practice use.