Correlation of Partial Discharge Pulse Signals in Transformer Windings to Locate Discharge Locations

桂峻峰,高文胜,谈克雄
DOI: https://doi.org/10.3321/j.issn:1000-0054.2003.03.007
2003-01-01
Abstract:The propagation of partial discharge pulses in transformer windings and the related signals at terminals outside the transformer were studied using tests and simulations to develop a method to locate partial discharge sources electrically. Equipment was built to imitate a partial discharge pulse current in transformer windings with the windings equivalent circuit analyzed in the simulation. The measured and simulated signals at the winding terminals agree reasonably well. An electrical method was developed to locate partial discharges in transformer windings by correlating the signal and the simulated response.
What problem does this paper attempt to address?