Investigation of the UHF Partial Discharge Detection Characteristics of a Novel Bushing Tap Sensor for Transformers

Jiangrong Cheng,Yuan Xu,Dengwei Ding,Weidong Liu
DOI: https://doi.org/10.1109/tpwrd.2020.3026102
IF: 4.825
2021-01-01
IEEE Transactions on Power Delivery
Abstract:HFCT method is a common detection technology for partial discharge (PD) in transformer. However, it suffers a lot from electromagnetic interference in field applications because conventional detection band of it is relatively low, usually in HF band. In this paper, a HFCT, which frequency response includes the whole of the VHF band and extends up to 500 MHz in the UHF band, is adopted to improve the anti-interference capacity of HFCT method. And we make a full investigation on the detection characteristics of HFCT method in UHF band based on an actual 220 kV transformer with complete internal structures. Four typical defects model is established as PD sources, additionally, conventional methods are also adopted in the experiment to make comparison with HFCT method in UHF band. The experiment results indicate that HFCT method can detect PD effectively in UHF band, and the detection sensitivity of it is no less than that of conventional methods. The results confirm the effectiveness of HFCT method in UHF band, therefore, the problem of low anti-interference capacity of conventional HFCT method that detects PD in HF band can be overcome. It offers a new effective and practical solution for transformer field monitoring of PD, especially for the transformers to which internal antenna UHF method can't be applied due to the lack of dielectric window.