Investigation on the Sensitivity of the UHF Method for Partial Discharge Detection in GIS

Xiao LI,Yang XU,Yong WANG,Xing LI,Jun XIONG,Weidong LIU
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.05.010
2018-01-01
Abstract:UHF detection of partial discharges (PD) in GIS has been widely used, however its capability of pre-warning the flashover failures of the GIS insulators is limited, causing a big concern on the sensitivity of the UHF method. Experimental investigation is made in this paper on the PDs in an actual GIS supporting insulator with actual defect, which demonstrates that the UHF method does have blind angle in sensitivity. The PD pulses of the supporting insulator change greatly in there steepness, causing great change of the frequency band of the RF signals from the PDs. Most of the PDs have RF signals lower than UHF band, and cannot be detected by UHF method. It means that serious PDs of the GIS insulator could possibly show UHF pulses of small amplitude and small density, and easily be neglected according to the current diagnosing criteria.