PD Test and Measurement Method of GIS Insulators Based on Cross-reference of the Pulse Current

Yang XU,Weidong LIU,Yuan XU,Xing LI,Zhibing LI,Pengfei ZHANG
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.05.014
2018-01-01
Abstract:Strict inspection of the GIS (or GIL) insulation parts is very important for ensuring the GIS manufacturing quality. The partial discharges (PD) of some GIS insulation defects are characterized by weak signal strength and small pulse density, and could be possibly missed by the conventional PD measurement method. It is presented in this paper a new method for PD test and measurement of GIS insulation parts which works based on cross-reference ofthe current pulses. In the method, more than one similar insulator are tested in parallel, the pulse currents in the grounding ends of each insulator are measured synchronously, and the PD pulses from the insulators are recognized according to the difference of the pulse amplitudes between the insulators. Taking the PD signals from the grounding end of the insulators also improves the SNR and increasrs the sensitivity of PD measurement. By the method the PD of weak strength and small density can be detected.