Research on the Typical Partial Discharge Using the UHF Detection Method for GIS

Wensheng Gao,Dengwei Ding,Weidong Liu
DOI: https://doi.org/10.1109/tpwrd.2011.2166089
2011-01-01
Abstract:GIS plays an important role in power systems for its maintenance-free and less influence to environmental and industrial conditions.In order to monitor the on-line condition,ultra high frequency(UHF) method is widely used for defect diagnosis of GIS.Therefore,five types of typical partial discharge(PD) sources were designed and fabricated to imitate the defects in GIS online.To distinguish the types of partial discharges,some meaningful parameters behind the UHF signal were extracted and discussed.In general,the conventional phase-resolved partial discharge(PRPD) and pulse sequence analysis method is adopted to discriminate partial discharge,but sometimes it may be less convenient to employ because of the absence of the phase information.Consequently,nine comprehensive parameters realized by processing the UHF pulse magnitude sequence q and time interval sequence Δt are introduced.The parameters can describe exactly the physical characteristics of different partial discharges.By means of the parameters,the pattern classification of PD without employing the phase information of the applied voltage could be achieved.The clustering results by SPSS indicate that there is evident difference in the characteristic coefficients.
What problem does this paper attempt to address?