On Site Detection and Localization of Partial Discharge in Hydropower Plant GIL/GIS Based on Ultra-high Frequency Technique

Lihua Li,Yang Liu,Feng Chen,Xinzhi Yang,Xing Li,Mingtao Yu
DOI: https://doi.org/10.1109/icopesa61191.2024.10743434
2024-01-01
Abstract:Partial discharge (PD) detection is an important method for diagnosis and assessment of insulation defects in gas- insulated switchgears (GISs) and gas-insulated transmission lines (GILs). The ultra-high frequency (UHF) method is widely used for on-site PD detection of GIL/GIS owing its good sensitivity and anti-interference performance. In this paper, PD detection and localization diagnosis of GIL/GIS equipment in a hydropower plant is conducted. PD signal is detected in the GIL/GIS B-phase at the outgoing line yard using the UHF technique. Then, based on localization analysis, it is finally determined that the PD source is located on the insulator between the disconnector and current transformer. According to the PD diagnosis, the insulator is replaced and the X-CT flaw detection result shows that there are two 1–2 mm gaps inside this insulator. Subsequently, the PD test in the factory shows that significant and stable PDs are provoked by the dismantled insulator. These fully confirm the accuracy of on-site PD detection and localization diagnosis. The research of this paper provides good guidance for on-site equipment maintenance and helps to improve equipment stability.