GIS Partial Discharge Detection via Ultra-high Frequency Signal in Lightning Impulse Process

王增彬,郑书生,许鹤林,高文胜,吕鸿,卢启付,李兴旺,王流火
DOI: https://doi.org/10.13296/j.1001-1609.hva.2013.10.014
2013-01-01
Abstract:The effectiveness of detecting GIS partial discharge(PD) via ultra-high frequency(UHF) signal in lightning impulse process was investigated experimentally. In this scheme, No.1 UHF sensor detected the electromagnetic wave signal around the impulse voltage generator for the reference signal; No.2 UHF sensor detected the signal radiating from the basin-type insulator. The results show that: ① By comparing the waveforms from the two sensors, PD signal can be distinguished from the interference signal; ②When PD happens in GIS, the signal from No.2 UHF sensor exhibits three pulse groups with different signal amplitude, density and distribution; ③PD signal appears at 4 μs after PD pulse starting, and it continues for about 5 μs. Conclusion can be drawn that the UHF method is effective and reliable for GIS PD detection in lightning impulse process.
What problem does this paper attempt to address?