Partial Discharge Initiating Process of Transformer Oil under Combined AC and DC Voltage

周远翔,沙彦超,聂德鑫,伍志荣,邓建刚,卢理成
2012-01-01
Abstract:As a critical parameter for the main insulation design of power transformer, available electric field strength is the important index of the technology and management level. The valve winding of converter transformer withstands several types of voltage, including AC, DC, combined AC-DC voltages. However, the analogous problem for converter transformer has not received enought attention. Therefore, based on broadband sensors and pulse electric methods, the initiating process of partial discharge of transformer oil under combined AC-DC voltage was studied by using needle-plate and plane-plane electrodes. Partial discharge inception voltages ~PDIV) of two electrodes under the different voltages were summarized. The results show that PDIV is not related to voltage types under needle-plate electrodes but only to voltage amplitude. The results also show that AC PDIV has little relation with DC pre-stressed voltage. The process of the dielectric breakdown caused by partial discharge was recorded with an initial velocity of about 1.8 km/s. The surface topography of plasma channel was observed by scanning electron microscope (SEM). And the amounts of chemical elements C, O, Cu and Si are in sequence from high to low by energy dispersive spectrum (EDS). At last, an ANSYS structural model of single bubble in oil was established. The simulation results show that electric fields are more easily distorted by bubbles, and non-uniformity coefficient f is about 1.6.