Influence of AC and DC Voltage Superposition on Partial Discharge of Composite Insulator

Xinyu Cao,Gang Wang,Yi Zhao
DOI: https://doi.org/10.16790/j.cnki.1009-9239.im.2016.12.012
2016-01-01
Abstract:Silicone rubber insulation materials were applied AC and DC voltage together, and the influ-ence of AC and DC voltage superposition on the partial discharge magnitude and repetition rate of insula-tion air gap was studied. The results indicate that when the AC voltage ripple is below the partial dis-charge extinction voltage, compared with the condition aplied DC voltage with no AC voltage ripple, the number of big discharge pulses increase, and the dischage repetition rate is much lower than the frequen-cy of AC voltage.
What problem does this paper attempt to address?